CEILING MOUNTED LAMINAR FLOW (PLANAR) SYSTEM

Each modular OT shall have Plan Air Ceiling in OR. The Plan Air ceiling shall be constructed out of 2mm thick extruded aluminum 1.6mm thick sheet (HINDALCO) of sizes2800x2400,
2400×1800 & 1800×1800 mm having six Nos. HEPA filters with spot efficiency of 99.99% 0.3 micron. All HEPA filters shall be factory tested and certified in accordance with DIN 1946 and DIN 4799.

 

All ceiling shall include integral lighting and composite air / light diffuser. Air and light diffuser made of two layer of mono filament precision woven polyester of uniform porosity with an area of sufficient resistance to create laminar from diffusers face and integral lighting provides an illumination level in excess of 15000 LUX in operating area and 10000 LUX other electronic stop-less dimming down 5% without flicker. An air change is defined as occurring when a volume of air equivalent to the volume of the room has been supplied to or removed from that room.

Flowr

ANTISTATIC CONDUCTIVE TILES FLOORING

A floor screed should be provided, flat to within a tolerance of +/- 3mm over any 3 metre area. Onto this sub-floor, a self — levelling compound should be laid prior to lying of the floor finish. Copper grounding strips (0.05 mm thick, 50 mm width) should be laid flat on the floor in the conductive adhesive and connect to copper wire of grounding . The floor finish in the operating room should be 2mm Conductive PVC tiles, laid on a semi-conductive adhesive base. The floor finish should terminate at the room perimeter passing over a concealed cove former and continuing up the wall for 100mm. All joints should be welded with electrodes of the same compatible material to provide a continuous sealed surface.

OPERATION THEATRE CONTROL PANEL

The surgeon control panel should meet Electrical safety codes for high & low voltage system, wired to the current IEE regulations. All the controls within the theatre are located on a membrance type control panel (6 &9 Tiles) mounted flush in the theatre wall with distribution board complete with all accessories. A remote electrical distribution board is provided to allow access to the panel of maintenance with access to the theatre.
The Panel should contain 6 or 9 service tiles as below:
1. Time Day Clock
2. Time Elapse Day Clock
3. General Lighting System
4. Medical Gas Alarm Pane15. Hand Free Telephone set with memory
6. Temperature & humidity indicator with controller
7. HEPA Filter Status module
8. Room Pressure Indicator
9. Music control